Setting Vsd MM44013


SETTING VSD MICROMASTER 420,440 (SIEMENS)


A. METHOD FOR QUICK COMMISSIONING

P10 =1,
START OF QUICK COMMISSIONING
P304 =MOTOR VOLTAGE RATING
P305 =MOTOR CRRENT
P307 =MOTOR POWER RATING (KW)
P308 =MOTOR COSØ RATING
P311 =MOTOR RPM RATING
P700 =SELECTION OF COMMAND SOURCE
=1, FOR MANUAL OPERATION
=5, FOR USS COMMUNICATION
=6, FOR PROFIBUS
P1000 =SELECTION OF COMMAND SOURCE
=1, FOR MANUAL OPERATION
=5, FOR USS COMMUNICATION
=6, FOR PROFIBUS COMMUNICATION
P1120 =RAMP UP TIME IN SECONDS (0-650SECONDS)
P1121 =RAMP DOWN TIME IN SECONDS (0-650SECONDS)
P3900 =1,
P305=Motor current ( Very important )
P610=1
P640=100
P290=1
                    B) MISCALENOUS PARAMETERS
P3 =3,TO SEE ALL THE PARAMETERS
R21 = TO CHECK THE MOTOR FREQUENCY
R27 = TO CHECK THE MOTOR CURRENT
P5 =DISPLAY SELECTIION
=21, FOR CONTINUOUSDISPLAY OF FREQUENCY
=27,FOR CONTINUOUS DISPLAY OF CURRENT
=25, FOR CONINUOUS DISPLAY OF VOLTAGE
P295 =INVERTER FAN OFF DELAY TIME (0-3600 SECONDS)
P918 =INVERTER PROFIBUS ADDRESS
R947 =LAST FAULT CODE
=947[0], FAULT 1
=947[1], FAULT 2
=947[2], FAULT 3
R949 =FAULT VALUE
=949[0], FAULT VALUE 1
=949[1], FAULT VALUE 2
=949[2], FAULT VAULE 3
R967 =CONTROL WORD1
P1820 =REVERSE OUTPUT PHASE SEQUENCE
P1031 =SETPOIT MEMORY OF THE MOP
=0, MOP SETPOINT WILL NOT BE STORED
=1, MOP SETPOINT WILL BE STORED
         C) PROCEDURE FOR FACTORY RESET
P10 =30
P970 =1

          D) PROCEDURE FOR SETTING USS COMMUNICATION
i) FACTORY RESET THE DRIVE
ii) PERFORM QUICK COMMISSIONING
P2012 =2, USS PZD LENGTH
P2013 =127, USS PKW LENGTH
P700 =5, COMMAND SOURCE SELECTION
P1000 =5, FREQUENCY SOURCE SELECTION
P2009 =0,
P2010 =BAUD RATE
=5, 4800 BAUD
=6, 9600 BAUD
=7, 19200 BAUD
=8, 38400 BAUD
=9, 57600 BAUD
=12, 115200 BAUD
P2011 = INVERTER USS ADDRESS (0-31)

   E) PROCEDDURE FOR SETTING IF HARD WIRE OUTPUTS ARE USED
i) FACTORY RESET THE DRIVE
ii) PERFORM QIUCK COMMISSIONING
P700 =2,TERMINAL INPUT
P701 =16, FIXED FREQUENCY 1
P702 =16, FIXED FREQUENCY 2
P1000 =3, FIXED FREQUENCY
P1001 =VALUE OF FIXED FREQUENCY 1 ( EXAMPLE 25 HZ)
P1002 =VALUE OF FIXED FREQUENCY 2 (EXAMPLE 25 HZ)

PROCEDURE TO GET 4-20 MILLI AMPERE FROM TERMINAL 12, 13 OF THE
DRIVE
P771 =21, IF OUTPUT IS NEEDED CORRESPONDING TO FREQUENCY
=27, IF OUTPUT IS NEEDED CORRESPONDING TO CURRENT
P778 =4, VALUE Y1 FOR DAC SCALING
P780 =20, VALUE Y2 FOR DAC SCALING
P777 =0, VALUE X1 FOR DAC SCALING
P779 =50.09, VALUE X2 FOR DAC SCALING
P776 =0, IF 1 IS SELECTED 0-10VDC WILL APPEAR ACROSS 12,13 (PROVIDED
500
R774 =ACTUAL DAC VALUE IN MA





(BREAKING RESISTOR IS CONNECTED BETWEEN 12,13 OF DRIVE)
Note to prevent the motor from getting failed due to over current**//END OF QUICK COMMISIONING