Harmonic currents and neutral conductors8
A perfectly balanced three-phase system (one with all three
phase loads identical in all respects) has no neutral current and thus has no
need of a neutral conductor. This is often so with motors, which are fed through
three core cables in most cases.
Many three-phase loads are made up of single-phase loads,
each connected between one line and neutral. It is not likely in such cases that
the loads will be identical, so the neutral will carry the out-of-balance
current of the system. The greater the degree of imbalance, the larger the
neutral current.
Some three-phase four-core cables have a neutral of reduced
cross-section on the assumption that there will be some degree of balance. Such
a cable must not he used unless the installer is certain that severe
out-of-balance conditions will never occur. Similar action must be taken with a
three-phase circuit wired in single-core cables. A reduced neutral conductor may
only be used where out-of-balance currents will be very small compared to the
line currents.
A problem is likely to occur in systems which generate
significant third harmonic currents. Devices such as discharge lamp ballasts and
transformers on low load distort the current waveform. Thus, currents at three
times normal frequency (third harmonics) are produced, which do not cancel at
the star point of a three-phase system as do normal frequency currents, but add
up, so that the neutral carries very heavy third harmonic currents. For this
reason, it is important not to reduce the cross-sectional area of a neutral used
to feed discharge lamps (including fluorescent lamps).
In some cases the neutral current may be considerably larger
than the phase currents. Where the load concerned is fed through a multi-core
cable, it may be prudent to use five-core (or even six-core) cables, so that two
(or three) conductors may be used in parallel for the neutral.
In some cases it may be necessary to insert overload
protection in a neutral conductor. Such protection must be arranged to open all
phase conductors on operation, but not the neutral. This clearly indicates the
use of a special circuit breaker.
It is very important that the neutral of each circuit is kept
quite separate from those of other circuits. Good practice suggests that the
separate circuit neutrals should be connected in the same order at the neutral
block as the corresponding phase conductors at the fuses or circuit
breakers.
Komentar
Posting Komentar